<%@ Language=VBScript %> Cold Shrinkable Power Cable Accessories,Cold Shrinkable Power Cable Termination,Straight Joints

 

About Us Certificate Contact Us Products

 

 
BackHome
Cold Shrinkable Power Cable Accessories
Summary for Cold Shrinkable Power Cable Terminations and Straight Joints

       Cold shrinkable power cable accessories, Cold shrinkable power cable termination and straight joint: Cold shrink technology makes the installation of cold shrinkable power cable accessories, cold shrinkable power cable termination and straight joint process simpler compared with traditional kits and reduces craft errors that may threaten reliability. After cold shrinkable power cable accessories,cold shrinkable power cable termination and straight joint installation, the cold shrink tube creates a dynamic, compressive environmental seal and electrical interface without sealants or adhesives. This seal retains resiliency and pressure even after several years of use and in temperature variations. Cold shrink tube is able to resist UV radiation and ozone.
Advantages:
cold shrinkable power cable accessories,cold shrinkable power cable termination and straight joint can be installed quickly and easily,
cold shrinkable power cable accessories, cold shrinkable power cable termination and straight joint have  low weight
cold shrinkable power cable accessories,cold shrinkable power cable termination and straight joint  have reliability and ability to work in different environments
cold shrinkable power cable accessories,cold shrinkable power cable termination and straight joint  can be used on a wide range of cables in a wide range of applications
cold shrinkable power cable accessories,cold shrinkable power cable termination and straight joint  is no need for heating means more safety for installers.

Specification Table of cold shrinkable power cable accessories,cold shrinkable power cable termination and straight joint

 

1-core cold shrinkable power cable accessories,cold shrinkable power cable termination and straight joint

Product name

Mode & specification

The applicable cable setction mm2

10kV One-core Indoor Termination

NLSY-10/1·1

25-50

NLSY-10/1·2

70-120

NLSY-10/1·3

150-240

NLSY-10/1·4

300-400

10kV One-core Outdoor Termination

WLSY-10/1·1

25-50

WLSY-10/1·2

70-120

WLSY-10/1·3

150-240

WLSY-10/1·4

300-400

10kV One-core Straight Joint

JLSY-10/1·1

25-50

JLSY-10/1·2

70-120

JLSY-10/1·3

150-240

JLSY-10/1·4

300-400

35kV One-core Indoor Termination

NLSY-35/1·1

25-50

NLSY-35/1·2

70-120

NLSY-35/1·3

150-240

NLSY-35/1·4

300-400

35kV One-core Outdoor Termination

WLSY-35/1·1

25-50

WLSY-35/1·2

70-120

WLSY-35/1·3

150-240

WLSY-35/1·4

300-400

35kV One- core Straight Joint

JLSY-35/1·1

25-50

JLSY-35/1·2

70-120

JLSY-35/1·3

150-240

JLSY-35/1·4

300-400


 

3-core cold shrinkable power cable accessories,cold shrinkable power cable termination and straight joint

Product name

Mode & specification

The applicable cable setction

10kV Three-core Indoor Termination

NLSY-10/3·1

25-50

NLSY-10/3·2

70-120

NLSY-10/3·3

150-240

NLSY-10/3·4

300-400

10kV Three-core Outdoor Termination

WLSY-10/3·1

25-50

WLSY-10/3·2

70-120

WLSY-10/3·3

150-240

WLSY-10/3·4

300-400

10kV Three-core Straight Joint

JLSY-10/3·1

25-50

JLSY-10/3·2

70-120

JLSY-10/3·3

150-240

JLSY-10/3·4

300-400

35KV Three-core Indoor Termination

NLSY-35/3·1

25-50

NLSY-35/3·2

70-120

NLSY-35/3·3

150-240

NLSY-35/3·4

300-400

35kV Three-core Outdoor Termination

WLSY-35/3·1

25-50

WLSY-35/3·2

70-120

WLSY-35/3·3

150-240

WLSY-35/3·4

300-400

35KV Three-core Straight Joint

JLSY-35/3·1

25-50

JLSY-35/3·2

70-120

JLSY-35/3·3

150-240

JLSY-35/3·4

300-400

Type Demonstration for Cold Shrinkable Power Cable Terminations and Straight Joints

Technical Data of  cold shrinkable power cable accessories,cold shrinkable power cable termination and straight joint
Product name

test name

standard requirement result remarks

10kV indoor, outdoor termination and straight joints

p.f withstand voltage test 45kV no flash and no breakdown 45kV no flash and no breakdown passed
test of partial discharge 13kV20pC 13kV,3pC passed
load circulation test 5h heated,3h cooled, conductor heated to 90-95 conductor heated to 90-95 total 3 circulations as follows
partial discharge test 13kV20pC 13kV,3pC passed
lmpulse voltage test 105kV, on negative and positive poles applied each 10tmes.one flashover is allowed but not calculated. 105kV no flash and no breakdown passed
test of the negative pole 52kV,15min no flash and no breakdown 52kV,15min no flash and no breakdown passed
4h power voltage test 35kV.4h no flash and no breakdown 35kV 4h no flash and no breakdown passed
Product name

test name

standard requirement result remarks

35kV indoor, outdoor termination and straight joints

p.f withstand voltage test 105kV no flash and no breakdown 105kV no flash and no breakdown passed
test of partial discharge  discharge is less than 10PC under 39kV Discharge is 40PC under 39kV for Sample passed
load circulation test 5h heated,3h cooled,conductor heated to 90-95 5h heated,3h cooled,conductor heated to 90-95℃  as follows
partial discharge test  discharge is less than 10PC under 39kV Discharge is 40PC under 39kV for Sample passed
lmpulse voltage test 250kV,on negative and positive poles applied each 10times,one flashover is allowed but not calculated.. 250kV,on negative and positive poles applied each 10times,one flashover is allowed but not calculated. passed
test of the negative pole 156kV,15min no flash and no breakdown 156kV,15min no flash and no breakdown passed
Power voltage test 104kV,4h no flash and no breakdown 104kV,4h no flash and no breakdown passed

1-Core Outdoor Termination

1-Core Indoor 
Termination

      3-core Indoor Cold Shrinkable Termination

3-core Outdoor Cold shrinkable Termination

 Cold Shrinkable Straight Joint